Single Layer Rupture discs - The father of all rupture discs

 

The rupture disc that started it all many decades ago. Even now, this forward acting  rupture disc is still a good choice for simple applications with medium to high pressures, such as in pumps, in the petrochemical and chemical industries or in hydraulics. The standard operating ratio is up to 70 %* of the minimum response pressure.
The burst pressure is determined by the tensile strength and thickness of the material. Also available with integrated vacuum support for total vacuum resistance.

*Depending on the specific application

Rupture disc / bursting disc ODV
REMBE® single layer rupture disc

Your advantages

  • Easy to use.
  • Wide range of materials available.

The BT rupture disc is of course a bit older than many of the others, but there is still a steady demand for it, and this hasn’t changed in all my 25 years at REMBE®. 

Karl-Josef Lünsdorf, rupture disc specialist up to DN 100

Images

chemical plant

 

Technical data
burst element Stainless Steel Nickel Inconel* Monel* Hastelloy* Aluminium
max. allowable temperature** 400 °C 400 °C 600 °C 430 °C 400 °C 120 °C
NPS [in] DN [mm] min. burst pressure [barg]
¼'' 6.35 40 27.5 60 50 70 15
½'' 15 30 11 21 20 43 6.0
¾'' 20 16 9.0 15 10 28 2.6
1'' 25 13 8.0 11 7.0 20 2.0
1½'' 40 10 4.5 8.0 6.0 15 1.5
2'' 50 6.0 3.2 7.5 4.5 10 1.0
2½'' 65 6.0 2.5 5.0 3.0 6.6 0.90
3'' 80 5.5 2.0 4.3 2.5 6.0 0.70
4'' 100 5.0 1.6 3.3 2.0 5.0 0.30
6'' 150 3.5 2.2 3.0 2.5 5.0 0.20
8'' 200 3.0 1.5 2.5 2.0 4.5 0.10
10'' 250 3.0 1.4 2.5 2.0 4.5 0.10
12'' 300 2.0 1.4 2.0 2.0 4.0 0.10
14'' 350 2.0 1.2 1.5 2.0 4.0 0.10
16'' 400 2.0 1.0 1.5 2.0 3.5 0.10
18'' 450 2.0 0.90 1.5 2.0 3.5 0.10
20'' 500 2.0 0.75 1.5 1.5 3.0 0.10
24'' 600 2.0 0.3 3.5 4.0 0.40 0.10

*Company names or trademarks combined with material descriptions are only used for description purposes. The product promoted is not product of the respective companies and trademarks.

 ** Different temperatures may apply for rupture discs with CE mark.
Standard tolerance ±10 % including manufacture tolerance.
Different sizes, pressure classes, temperatures, materials and fittings available on request.

send enquiry